Implemented CANopen Objects
CAN-CBX-AI420
Manual • Doc.-No.: C.3030.21 / Rev. 1.4
Page 73 of 103
7.9.20 Verify Configuration (1020
h
)
INDEX
1020
h
Name
verify configuration
Data type
unsigned 32
Default value
No
In this object the date and the time of the last configuration can be stored to check later whether the
configuration complies with the expected configuration or not.
The content of the parameters is not evaluated by the firmware.
Index
Sub-
index
Description
Value range
Default
Data type
Access
mode
1020
h
0
no_of_entries
2
2
unsigned 8
ro
1
configuration_date
0...FFFFFFFF
h
0
unsigned 32
rw
2
configuration_time
0...FFFFFFFF
h
0
unsigned 32
rw
Parameter Description:
configuration_date
Date of the last configuration of the module. The value is defined in
number of days since the 01.01.1984.
configuration_time
Time in ms since midnight at the day of the last configuration.