Device Profile Area
Manual • Doc.-No.: C.3030.21 / Rev. 1.4
CAN-CBX-AI420
Page 84 of 103
7.10.6 Global Interrupt Enable (6423
h
)
Index
Sub-
index
Description
Value range Default
Data
type
Access
mode
6423
h
0
Analog_Input_Global_Interrupt_Enable
true, false
false
boolean
rw
With the object Analog Input Global Interrupt Enable the interrupt function of the module is
enabled or disabled. The values in object 6421
h
and 6426
h
remain unaffected of this.
In the default-setting the interrupts are disabled.
Value range:
Analog_Input_Global_Interrupt_Enable
Value
Meaning
true
1
Global Interrupt enabled
false
0
Global Interrupt disabled
(default setting)
Note:
It is mandatory to set Analog_Input_Global_Interrupt_Enable to ‘true’, in order that an
event-triggered transmission of the TPDO can be started.