Manufacturer Specific Profile Area
Manual • Doc.-No.: C.3030.21 / Rev. 1.4
CAN-CBX-AI420
Page 94 of 103
7.11.6 Accu N (2402
h
)
Index
Sub-
index
Description
Value range
Default
Data type
Access
mode
2402
h
0
Number of entries
4
4
unsigned 8
ro
1
Accu_Count_1
0...8
0
unsigned 8
rw
2
Accu_Count_2
0...8
0
unsigned 8
rw
3
Accu_Count_3
0...8
0
unsigned 8
rw
4
Accu_Count_4
0...8
0
unsigned 8
rw
This object defines, how many analog values are to be added up.
By the appropriate pre-processing of the output value of the A/D-converter the result of this addition
is always a 16-bit value in the two’s complement representation.
The number of additions is calculated as:
number of additions = n
n = 2
(Accu_Count_x)
Up to 256 values can be added up.
Advantage:
Filter with decimation, improvement of the resolution, limitation of the data rate.