4. Troubleshooting (PROFIBUS DP)
300
RC700 / RC90 Option Fieldbus I/O Rev.14
Slave: Uninitialized Network
BF
ST
Master LED Condition
Light OFF
Red Light Blinking
Absent Slave LED Condition
(Uninitialized Network)
Light OFF
Light OFF
♦
Process Flowchart
4
No Problem
Check
Check the following:
- Unconnected terminating resistor
- Unconnected or loose connector/signal wire
- Cable disconnection
Finish
Measure voltage of all
slave power supplies.
No Problem
No Change
No
Problem exists. (Fix it.)
Problem exists. (Fix it.)
The problem is fixed.
No problem
No problem
No change
Replace the unit.
Yes
No
See 4.2.3.1 and 4.2.3.2.
Consult the PROFIBUS manufacturer.
Replace moving cable.
(Replace deteriorated cable).
Normal Communication?
Содержание RC700
Страница 1: ...Robot Controller RC700 RC90 Option Fieldbus I O Rev 14 EM198C4088F ...
Страница 2: ...Robot Controller RC700 RC90 Option Fieldbus I O Rev 14 ...
Страница 8: ...vi RC700 RC90 Option Fieldbus I O Rev 14 ...
Страница 12: ...Table of Contents x RC700 RC90 Option Fieldbus I O Rev 14 ...
Страница 74: ...2 Installation 62 RC700 RC90 Option Fieldbus I O Rev 14 17 DeviceNet Slave is connected and the icon appears ...
Страница 165: ...2 Installation RC700 RC90 Option Fieldbus I O Rev 14 153 PCI CIFX 50 RE PCI Express CIFX 50E RE ...
Страница 183: ...2 Installation RC700 RC90 Option Fieldbus I O Rev 14 171 17 EtherNet IP Slave is connected and the icon appears ...
Страница 340: ...5 Maintenance Parts List 328 RC700 RC90 Option Fieldbus I O Rev 14 ...