4. Troubleshooting (DeviceNet)
RC700 / RC90 Option Fieldbus I/O Rev.14
279
♦
Process Flowchart
Check that
terminating resistors
are connected.
Measure resistance
with tester.
50 to 70
Ω
Normal
See 4.1.3.2.
Turn OFF communications power supply.
Normal
Resistance: over 70
Ω
Remove one terminating
resistor on either side.
Measure
resistance at
connectors and
branch taps with
tester.
Resistance: under 50
Ω
Problem exists.
(Add terminating resistors.)
Out of 50 to 70
Ω
(Error)
Yes
Other
Approx.
120
Ω
10 to 50
Ω
Under 10
Ω
No
(1) Unconnected or loose connector
(2) Cable disconnection, etc.
(1) Three or more
terminating resistors
(2) Wrong terminating
resistors, etc.
Short
circuit
between signal
wires
Check for cable laying.
Find the trouble point.
Check for connection
with terminating resistors
and branch taps.
Check for short
circuit between
signal wires.
Содержание RC700
Страница 1: ...Robot Controller RC700 RC90 Option Fieldbus I O Rev 14 EM198C4088F ...
Страница 2: ...Robot Controller RC700 RC90 Option Fieldbus I O Rev 14 ...
Страница 8: ...vi RC700 RC90 Option Fieldbus I O Rev 14 ...
Страница 12: ...Table of Contents x RC700 RC90 Option Fieldbus I O Rev 14 ...
Страница 74: ...2 Installation 62 RC700 RC90 Option Fieldbus I O Rev 14 17 DeviceNet Slave is connected and the icon appears ...
Страница 165: ...2 Installation RC700 RC90 Option Fieldbus I O Rev 14 153 PCI CIFX 50 RE PCI Express CIFX 50E RE ...
Страница 183: ...2 Installation RC700 RC90 Option Fieldbus I O Rev 14 171 17 EtherNet IP Slave is connected and the icon appears ...
Страница 340: ...5 Maintenance Parts List 328 RC700 RC90 Option Fieldbus I O Rev 14 ...