4. Troubleshooting (DeviceNet)
276
RC700 / RC90 Option Fieldbus I/O Rev.14
4.1.2.6 Uninitialized Network
Master Unit LED
Error
Description
MS
NS
Light OFF Light OFF Uninitialized network
Absent slave
- Master unit start-up error
- No slave (Error detection before
communication establishment)
- Communications power supply OFF
♦
Process Flowchart
9
No Problem
Check
Check the following:
- Unconnected terminating resistor
- Unconnected or loose connector/signal wire
- Cable disconnection
Finish
No Problem
No Problem
No Problem
Problem exists. (Fix it.)
Problem exists. (Fix it.)
Problem exists. (Fix it.)
Problem exists. (Fix it.)
No problem
No problem
No problem
No problem
Measure voltage of
communications power supply
at the master unit.
Check that power is supplied to all slaves.
Check for master unit configuration.
Replace the master unit.
See 4.1.3.1 and 4.1.3.2.
Содержание RC700
Страница 1: ...Robot Controller RC700 RC90 Option Fieldbus I O Rev 14 EM198C4088F ...
Страница 2: ...Robot Controller RC700 RC90 Option Fieldbus I O Rev 14 ...
Страница 8: ...vi RC700 RC90 Option Fieldbus I O Rev 14 ...
Страница 12: ...Table of Contents x RC700 RC90 Option Fieldbus I O Rev 14 ...
Страница 74: ...2 Installation 62 RC700 RC90 Option Fieldbus I O Rev 14 17 DeviceNet Slave is connected and the icon appears ...
Страница 165: ...2 Installation RC700 RC90 Option Fieldbus I O Rev 14 153 PCI CIFX 50 RE PCI Express CIFX 50E RE ...
Страница 183: ...2 Installation RC700 RC90 Option Fieldbus I O Rev 14 171 17 EtherNet IP Slave is connected and the icon appears ...
Страница 340: ...5 Maintenance Parts List 328 RC700 RC90 Option Fieldbus I O Rev 14 ...