"Alarm" submenu
Navigation
Setup → Advanced setup → Application → Alarm → Alarm
→ Alarm mode
Alarm mode
Navigation
Setup → Advanced setup → Application → Alarm → Alarm → Alarm mode
Description
Defines the alarm mode of the selected alarm.
Selection
• Off
• On
• Latching
Factory setting
Off
Additional information
Read access
Operator
Write access
Maintenance
Meaning of the options
•
Off
No alarms are generated.
•
On
An alarm disappears if the alarm condition is no longer present (taking into
consideration the hysteresis).
•
Latching
All alarms remain active until the user selects
Clear alarm (→ 221)
=
Yes
or the
power is switched off and on.