Operating menu
Tankside Monitor NRF81
134
Hauser
Additional information
Read access
Operator
Write access
-
Process variable
Navigation
Setup → Advanced setup → Input/output → Analog IP → Process variable
Prerequisite
Operating mode (→ 132)
RTD temperature input
Description
Determines type of measured value.
Selection
• Level linearized
• Temperature
• Pressure
• Density
Factory setting
Level linearized
Additional information
Read access
Operator
Write access
Maintenance
0 % value
Navigation
Setup → Advanced setup → Input/output → Analog IP → 0 % value
Prerequisite
Operating mode (→ 132)
4..20mA input
Description
Defines the value represented by a current of 4mA.
User entry
Signed floating-point number
Factory setting
0 mm
Additional information
Read access
Operator
Write access
Maintenance
100 % value
Navigation
Setup → Advanced setup → Input/output → Analog IP → 100 % value
Prerequisite
Operating mode (→ 132)
4..20mA input
Description
Defines the value represented by a current of 20mA.
Содержание NRF81
Страница 250: ...www addresses endress com 71406899 71406899...