Operating menu
Tankside Monitor NRF81
184
Hauser
Factory setting
0 bar
Additional information
Read access
Operator
Write access
Maintenance
P2 offset
Navigation
Setup → Advanced setup → Application → Tank configuration → Pressure → P2
offset
Description
Defines the offset for the middle pressure (P2). The offset is added to the measured
pressure prior to any tank calculation.
User entry
–25 to 2.5 bar
Factory setting
0 bar
Additional information
Read access
Operator
Write access
Maintenance
P1-2 distance
Navigation
Setup → Advanced setup → Application → Tank configuration → Pressure → P1-2
distance
Description
Defines the distance between the bottom and the middle pressure transmitter.
User entry
0 to 100
000 mm
Factory setting
2
000 mm
Additional information
Read access
Operator
Write access
Maintenance
P2 absolute / gauge
Navigation
Setup → Advanced setup → Application → Tank configuration → Pressure → P2
absolute / gauge
Description
Defines whether the connected pressure transmitter measures an absolute or a gauge
pressure.
Selection
• Absolute
• Gauge