Operating menu
Tankside Monitor NRF81
212
Hauser
User entry
0 to 3
000 kg/m³
Factory setting
800 kg/m³
Additional information
Read access
Maintenance
Write access
Maintenance
Density value
Navigation
Setup → Advanced setup → Application → Tank calculation → HTMS → Density value
Description
Shows the calculated product density.
Additional information
Read access
Operator
Write access
-
Minimum level
Navigation
Setup → Advanced setup → Application → Tank calculation → HTMS → Minimum
level
Description
Defines the minimum product level for a HTMS calculation. If Lp - V falls below the limit
defined in this parameter, the density retains its last value or the manual value is used
instead.
User entry
0 to 20
000 mm
Factory setting
7
000 mm
Additional information
Read access
Operator
Write access
Maintenance
Minimum pressure
Navigation
Setup → Advanced setup → Application → Tank calculation → HTMS → Minimum
pressure
Description
Defines the minimum pressure for a HTMS calculation. If the pressure P1 falls below the
limit defined in this parameter, the density retains its last value or the manual value is
used instead.
User entry
0 to 100 bar
Factory setting
0.1 bar