Tankside Monitor NRF81
Operating menu
Hauser
197
Additional information
Read access
Operator
Write access
Maintenance
The
Covered
option is only valid for fixed tank roofs. For a floating roof select
Open
top
.
Stilling well
Navigation
Setup → Advanced setup → Application → Tank calculation → CTSh → Stilling well
Description
Determines whether the device is mounted on a stilling well.
Selection
• No
• Yes
Factory setting
No
Additional information
Read access
Operator
Write access
Maintenance
Calibration temperature
Navigation
Setup → Advanced setup → Application → Tank calculation → CTSh → Calibration
temperature
Description
Specify temperature at which the measurement has been calibrated.
User entry
–50 to 250 °C
Factory setting
25 °C
Additional information
Read access
Operator
Write access
Maintenance
Linear expansion coefficient
Navigation
Setup → Advanced setup → Application → Tank calculation → CTSh → Linear
expansion coefficient
Description
Defines the linear expansion coefficient of the tank shell material.
User entry
0 to 100 ppm
Factory setting
15 ppm