Commissioning
Tankside Monitor NRF81
68
Hauser
9.2.8
Tank calculation: Hybrid tank measurement system (HTMS)
HTMS uses level and pressure measurements to calculate the density of the medium.
In non-atmospheric (i.e. pressurized) tanks it is recommended to use the
HTMS
P1+P3
mode. Two pressure sensors are required in this case. In atmospheric (i.e.
unpressurized) tanks the
HTMS P1
with only one pressure sensor is sufficient.
2
4
D1
1
3
2
4
5
1
D3
3
A
B
D1
A0029275
A
The "HTMS P1" measurement mode
B
The "HTMS P1+P3" measurement mode
D1 P1 position
D3 P3 position
1
Level transmitter (e.g. typically FMR540 or FMR51)
2
Tankside Monitor
3
To inventory management system
4
Pressure sensor (bottom)
5
Pressure sensor (top)
1. Navigate to Setup → Advanced setup → Application → Tank configuration → Level
2. Go to
and specify from which device the level is obtained.
3. Navigate to Setup → Advanced setup → Application → Tank configuration → Pressure
4. Go to
P1 (bottom) source (→ 181)
and specify from which device the bottom
pressure (P1) is obtained.
5. If a top pressure transmitter (P3) is connected:
Go to
P3 (top) source (→ 185)
and specify from which device the bottom
pressure (P1) is obtained.
6. Navigate to: Setup → Advanced setup → Application → Tank calculation → HTMS
7. Go to
8. Navigate to Setup → Advanced setup → Application → Tank configuration → Density
9. Go to
Observed density source (→ 179)
and select
HTMS
.
10. Use the other parameters of the
HTMS
submenu to configure the calculation. For a