Tankside Monitor NRF81
Operating menu
Hauser
201
HTG evaluation: dependence on measured level
To calculate the level or density by HTG with the required accuracy, P1 and P2 have to be
covered by a certain product level. To avoid a measurement with an insufficient accuracy,
the calculation will stop before the level reaches the position of the pressure sensor.
Two parameters are defined for this purpose:
•
Minimum level
This parameter defines the position below which no level is accepted. If the calculation
leads to
Tank level
<
Minimum level
, the value of
Minimum level
will be displayed
instead of the calculated value.
•
Safety distance
This parameter defines the minimum amount of product which must be present above
the pressure sensor P1 or P2 for the level or density calculation to take place.
• The device always uses the bigger of these two values as the switch-over point for
the level calculation.
• If
P1 only
or
P1 + P3
, the density is not calculated
and the
Manual upper density
parameter is used instead.
Case 1: H
P1
< Minimum level < H
P2
A
B
C
3
P3
P2
P1
1
2
5
4
A0028718
1
2
Safety distance (→ 208)
3
P1-2 distance (→ 184)
4
Safety distance (→ 208)
5
Level L is in area
Calculation method for ρ
P
Calculation method for L
A
calculated from pressure
calculated from pressure
B
ρ
P
held
calculated from pressure
C
ρ
P
held
L =
Minimum level