Micropilot S FMR531 with HART/4...20 mA
Commissioning
E Hauser
57
Function "dip table" (035)
This function edits the dip value.
Function "dip table handl." (036)
Use this function to enter the dip value (level or distance) which will correct the measurement
values.
Selection:
•
new point
• edit point
• store point
• delete point
• return
• next point
• previous point
General procedure:
To enter a new point into the dip table, use
"
new point
" to enter the value (pairs),
"
store point
" to sort the new value (pairs,
"
return
" to go to the dip table mode and
"
table on
" to activate the dip table.
new point
You can enter a new point. Suggested values displayed for the measured value and dip value are the
current uncorrected level or remaining fill height. The new value pair can be altered without
selecting the "
edit point
" parameter. If the table is full, you can still select this parameter. In this
case, the number of free table entries stands at minimum value (
= 0
).
edit point
The displayed value pair can be changed. Only the dip value can be changed with semi-automatic
input mode.
"
Caution!
To accept the value pair in the table, confirm it with "
store point
".
⇒
E HAUSER
E
+
–
⇒
E HAUSER
E
+
–