Commissioning
Micropilot S FMR531 with HART/4...20 mA
56
E Hauser
manual
The "manual mode" of the dip table can be used to enter collected data after a series of data pairs
taken at different tank levels. The parameter "manual" in the "
dip table
"
(033)
function can be used
to enter data pairs, which have been recorded at different levels, into the dip table. The measured
value and the dip value can be entered.
–
uncorrected measured value:
This is the measured value supplied by the instrument,
NOT
corrected by the dip table. The
choice of measured value, level or remaining fill height is dependent on the instrument setting.
– Dip value:
This is the level or distance to flange respectively, given by the hand dip. This value should be
used to correct the measured value.
!
Note!
The bigger the distance between the different levels while taking hand dips, the more accurate the
linearisation of the dip table will be.
semi-automatic
The value pairs in the dip table can be read. You can enter the dip value only. When there are new
value pairs, the current uncorrected level or distance is accepted as the measured value.
table on
The dip table is switched on.
table off
The dip table is switched off.
clear table
The complete dip table is deleted. The table is switched off. The number of free table entries is set
to the maximum value (
= 32
).
View
The value pairs in the dip table can
only
be read. You can still select this menu option, even if there
is no dip table available. In this case, the number of free table entries is at maximum value (
= 32
).
Function "dip table" (034)
This function edits measured variable. The number behind the entry "
remain
" indicates the current
number of remaining free value pairs. The maximum number of value pairs is 32; after each entry,
the remaining number is decremented.
!
Note!
The
un
corrected measured value is displayed in the "
dip table
" (
034
) function. This may differ
considerably from the measured values when a dip table is activated.
⇒
E HAUSER
E
+
–
Содержание Micropilot S FMR531
Страница 4: ...Brief overview Micropilot S FMR531 with HART 4 20 mA 4 Endress Hauser ...
Страница 87: ...Micropilot S FMR531 with HART 4 20 mA Technical data Endress Hauser 87 ...
Страница 98: ...Micropilot S FMR531 with HART 4 20 mA Index 98 Endress Hauser ...
Страница 100: ...www endress com worldwide BA207F 00 en 04 09 71093754 CCS FM SGML 6 0 ProMoDo 71093754 ...