Micropilot M FMR 240 with PROFIBUS PA
Commissioning
E Hauser
69
display (008)
The
distance
measured from the reference point to the product surface and the
level
calculated with the aid of the empty adjustment are displayed. Check whether the
values correspond to the actual level or the actual distance. The following cases can
occur:
•
Distance correct
−
level correct
→
continue with the next function, "
check
distance
"
(051)
•
Distance correct
−
level incorrect
→
Check "
empty calibr.
"
(005)
•
Distance incorrect
−
level incorrect
→
continue with the next function, "
check
distance
"
(051)
⇒
⇒
⇓
After 3 s, the following message appears