Micropilot M FMR 240 with PROFIBUS PA
Commissioning
E Hauser
73
6.5
Basic Setup with the ToF Tool
To carry out the basic setup with the ToF Tool operating program, proceed as follows:
•
Start the ToF Tool operating program and establish a connection
•
Select the "
basic setup
" function group in the navigation bar
"
Caution!
When using FMR 240 with
Wave Guide antenna
"
stilling well
" must be selected in the
"
tank shape
"
(002)
funktion.
The instrument is calibrated on delivering. The following parameters are default:
•
"
tank shape
"
(002)
- "
stilling well
",
please don’t change!
•
"
pipe diameter
"
(007)
- ~21 mm,
please don’t change!
•
"
empty calibr.
"
(005)
- zero point=pipe end,
possible readjust!
•
"
full calibr.
"
(006)
- span=reference point (
→
Page 59),
possible readjust!
The following display appears on the screen:
Basic Setup step 1/4:
•
Status image
•
Enter the measuring point description (TAG number).
L00-FMR2xxxx-20-00-00-en-001
!
Note!
•
Each parameter that is changed must be confirmed with the
RETURN
key!
•
The "
Next
" button moves you to the next screen display: