Operation
Micropilot M FMR 240 with PROFIBUS PA
48
E Hauser
5.5.6
Slot/index tables
The device parameters are listed in the following tables. The parameters are accessed
via the slot and index number.
The Analog-Input and physical blocks contain standard parameters, block parameters
and manufacturer-specific parameters. The transducer block of the Micropilot M is E+H
specific.
The parameters of the Analog-Input block are not available when operating via the
display or via ToF Tool.
Device Management
Analog-Input-Block
Parameter
E+H Matrix
(CW II)
Slot
Index
Size
[bytes]
Type
Read
Write
Storage
Class
Directory object
header
1
0
12
Array of
UNSIGNED16
X
constant
Composite list
directory entries
1
1
24
Array of
UNSIGNED16
X
constant
GAP Directory
continuous
1
2-8
GAP reserved
1
9-15
Parameter
E+H Matrix
(CW II)
Slot
Index
Size
[bytes]
Type
Read
Write
Storage
Class
Standard parameters
Block Data
1
16
20
DS-32*
X
constant
Static revision
1
17
2
UNSIGNED16
X
non-vol.
Device tag
1
18
32
OSTRING
X
X
static
Strategy
1
19
2
UNSIGNED16
X
X
static
Alert key
1
20
1
UNSIGNED8
X
X
static
Target Mode
1
21
1
UNSIGNED8
X
X
static
Mode
1
22
3
X
dynamic
non-vol.
constant
Alarm summary
1
23
8
X
dynamic
Batch
1
24
10
X
X
static
Gap
1
25
Block parameters
Out
V6H2 (Wert)
V6H3
(Status)
1
26
5
DS-33*
X
dynamic
PV Scale
V0H5
V0H6
1
27
8
Array of
FLOAT
X
X
static
Out Scale
1
28
11
DS-36*
X
X
static
Linearisation type
1
29
1
UNSIGNED8
X
X
static
Channel
1
30
2
UNSIGNED16
X
X
static
Gap
1
31
PV fail safe time
1
32
4
FLOAT
X
non-vol.
Fail safe type
1
33
1
UNSIGNED8
X
X
static