Micropilot M FMR 240 with PROFIBUS PA
Appendix
E Hauser
105
Output
The Micropilot is commissioned by entering an empty distance E (=zero), a full distance
F (=span) and an application parameter. The application parameter automatically
adapts the instrument to the process cond.. The data points “E” and “F” correspond with
4mA and 20mA for instruments with current output. They correspond with 0 % and
100 % for digital outputs and the display module.
A linearization with max. 32 points, based on a table entered either manually or
semi-automatically, can be activated locally or remotely. This function provides a
measurement in engineering units and a linear output signal for spheres, horizontal
cylindrical tanks and vessels with conical outlet.
11.4.2
Equipment architecture
Stand-alone
The Micropilot M with PROFIBUS PA can be used for measurement in a stilling well /
bypass as well as in free space.
System integration via PROFIBUS PA
The complete measuring system consists of:
L00-FMR2xxxx-14-00-06-en-002
E HAUSER
E HAUSER
E
+
–
%
FXA 193
PROFIBUS DP
PROFIBUS PA
personal computer
e.g. with
Commuwin II or
ToF Tool and
Profiboard resp. Proficard
segment coupler
PLC
operating and
display module
VU 331
ToF Tool