Logic Input
If the PS1 and PS2 terminals are linked in the control unit, the logic contact is made,
and the plant status is
OFF
. You may link these terminals manually during a plant
shut down, or you may wire them to a switch/contact outside the unit (e.g., a value
that opens and closes the duct). Press ENTER to select this option when the Plant
Status
→
Serial Input option is displayed.
•
Serial input
If you select this option, the criteria controlling plant status are transmitted via the
serial data link. Press ENTER when the Plant Status I/P
→
Serial Input option is
displayed to select this option.
•
Multiple
Four options are available here. Press ENTER when the Plant Status I/P
→
Multiple
option is displayed, and the first option
Temperature
is displayed. Use the arrow keys
to toggle
YES
or
NO
.
NO
means that the temperature threshold is not used to
determine plant status. If you select
YES
, the display enters the display below.
Configure the instrument for temperature threshold. Press ENTER when it is
correctly configured, and the display moves to the next option
Oxygen
. After you set
the last option, the Logic Input display returns to the PARAMETERS
→
Plant Status I/P
option. Use the DOWN arrow to scroll down to
EXIT
and press ENTER. The plant
status is now full configured.
Plant status is only
OFF
if all options selected are registering plant status
OFF
. If any
one of them is not fulfilling plant status
OFF
conditions, then the instrument
registers plant status
ON
.
-
Temperature
A value is set here for the temperature threshold. While the temperature (taken
from the normalizing temperature) is above the threshold value, plant status is
ON
. If the temperature drops below the threshold, plant status is
OFF
, and only
the seconds averaging stack updates.
-
Oxygen
Oxygen is set and used in a similar manner to the temperature threshold.
However, if the normalizing oxygen level rises above the threshold, plant status
is
OFF
. For plant status
ON
, the oxygen level must be below the threshold.
-
Water Vapor
Operation
68
Rosemount CCO 5500
Содержание Rosemount CCO 5500
Страница 1: ...Reference Manual 00809 0100 4550 Rev AA June 2018 Rosemount CCO 5500 Carbon Monoxide CO Analyzer ...
Страница 4: ......
Страница 8: ...Contents iv Rosemount CCO 5500 ...
Страница 28: ...System Wiring Diagram Figure 2 7 Install 20 Rosemount CCO 5500 ...
Страница 32: ...Install 24 Rosemount CCO 5500 ...
Страница 88: ...Operation 80 Rosemount CCO 5500 ...
Страница 98: ...Maintenance 90 Rosemount CCO 5500 ...
Страница 108: ...Troubleshooting 100 Rosemount CCO 5500 ...
Страница 110: ...Spare parts 102 Rosemount CCO 5500 ...
Страница 122: ...Return equipment to the factory 114 Rosemount CCO 5500 ...
Страница 123: ...Return equipment to the factory Reference Manual 115 ...