Receiver Test Points
Figure 3-3:
A. S1 white
B. S2 blue
C. S0V green
D. Voltage indication LEDs
3.
Adjust the alignment until the bright red disc of the source is located centrally in the
field of view when viewed from the receiver air purge. When the source unit is
aligned, tighten the locking nuts.
4.
Install and tighten the receiver on its air purge using the four screws removed in
5.
At the control unit keypad, press MODE four times to select
SET UP
mode (Mode
5
).
When
5 (SET UP)
is displayed on the LCD, press ENTER to access the
SET UP
mode.
Note
The analyzer uses a security code to prevent unauthorized alteration of settings. The default
code set at the factory is
0000
.
The keypad cursor flashes over the first digit of the security code.
Configuration and startup
28
Rosemount CCO 5500