Select whether the threshold value is to be specified per parameter or via a communi-
cation object.
When the
threshold value per parameter
is specified, then the value is set.
When the
threshold value per communication object
is specified, the starting val-
ue, object value limit and type of change to the threshold value are then set.
With both of the methods for specifying the threshold values the hysteresis is set.
Switching output
Define which value the output transmits if the threshold value is exceeded or undercut.
Set the delay for the switching and in which cases the switch output transmits.
Threshold value setpoint using
Parameter • Communications object
Threshold value in kLux
1 … 1000; 10
Start threshold value in Lux
valid until first call
1 … 1000; 10
Object value limit (min.) in Lux
1 … 1000
Object value limit (max.) in Lux
1 … 1000
Type of threshold change
Absolute value • Increase/decrease
Increment in Lux
(upon increase/decrease change)
1000 • 2000 • 5000 • 10000 • 20000
Hysteresis setting
in % • absolute
Hysteresis in % of the threshold value
(for setting in %)
0 … 100; 50
Hysteresis in Lux
(for absolute setting)
0 … 1000; 5
When the following conditions apply, the
output is
(LV = Threshold value)
• GW above = 1 | GW - Hyst. below = 0
• GW above = 0 | GW - Hyst. below = 1
• GW below = 1 | GW + Hyst. above = 0
• GW below = 0 | GW + Hyst. above = 1
Delays can be set via objects
(in seconds)
No • Yes
Delay from 0 to 1
none • 1 s … 2 h
Delay from 1 to 0
none • 1 s … 2 h
Switching output sends
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Cycle
(if sent periodically)
5 s ... 2 h