71
Parameter setting
Weather Station Suntracer KNX sl
• Version: 14.07.2016 • Technical changes and errors excepted.
Specify below which brightness the device should recognise "night" and with which
hysteresis this is to be outputted.
Set the delay for the switching and in which cases the switch output sends and which
value is output at night.
6.11. Sun position
Select whether the device should calculate the sun position itself or if the values are
received via the bus. The type of object and send pattern are also set.
6.12. Wind measurement
If necessary, activate the wind malfunction object. Specify whether the measurement
should also be output in Beaufort.
Night is recognised below
Lux
1 ... 1000; 10
Hysteresis in Lux
0 ... 500; 5
Delays can be set via objects
(in seconds)
No • Yes
Switching delay on night
none • 1 s … 2 h
Switching delay on day
none • 1 s … 2 h
Switching output sends
• on change
• on change to night
• on change to day
• on change and periodically
• on change to night and periodically
• on change to day and periodically
Send cycle
(if sent periodically)
5 s ... 2 h
Object value at night
0 • 1
Sun position
is calculated • is received
Object type
4 Byte floating point • 2 Byte floating point
Send pattern
(if the sun position is calculated by the
device)
• never
• periodically
• on change
• on change and periodically
on change of
(if sent on change)
0.1 degrees • 0.2 degrees • 0.5 degrees •
1.0 degree • 2.0 degrees • 5.0 degrees
Send cycle
(if sent periodically)
5 s ... 2 h; 1 min
Use malfunction object
No • Yes
Measured value additionally
output in the Beaufort scale
No • Yes