109
Parameter setting
Weather Station Suntracer KNX sl
• Version: 14.07.2016 • Technical changes and errors excepted.
Please observe: The slant of the façade and the angle set for the height of the sun
should be compatible. Thus, if the façade is slanted forwards by 10°, then the sun only
needs to be considered up to a height of 80°. Enter this separately with the parameters
the parameter for sun direction and height (see chapter
solar protection automation
,
Sun position
, Seite 103).
Intermediate position for the short retraction delay time
Solar protection automation moves to the "short delay" position if
•
the shading has been extended by the solar protection automation and
•
the brightness is then below the value (threshold value - hysteresis)
•
for longer than the short delay time.
For the movement position "short retraction delay" a movement position and a slat po-
sition can be set. Settings for slats are only displayed if the shading for the façade has
been defined as having slats (see
Façade safety
, Seite 94).
Standard movement position
Solar protection automation is terminated and the standard position is approached.
•
the sun is not coming from the set shading direction or
•
the brightness is then below the value (threshold value - hysteresis)
•
for longer than the time (short delay + retraction delay time).
Settings for slats are only displayed if the shading for the façade has been defined as
having slats (see
Façade safety
, Seite 94).
Status output façade
Information on the various possibilities for the status output can be found in chapter
Status output
, Seite 87. In principal the status output is a singular function, but, in com-
pact form, possible for singular and for all façades possible. The texts for the output in
compact form are defined in the general settings for the façade (see chapter
Status out-
put
, Seite 87).
Maximum depth of penetration
by the sun into the room in cm
10 ... 250; 50
From a shadow shift of
cm auto-tracking is performed
1 ... 50; 10
Use movement position
No • Yes
Movement position (in %)
0 ... 100
Use slat position
No • Yes
Slat position (in %)
0 ... 100
Move to position, if no automation with higher priority is being executed
Movement position (in %)
0 ... 100
Slat position (in %)
(only for window shades with slats)