100
Parameter setting
Weather Station Suntracer KNX sl
• Version: 14.07.2016 • Technical changes and errors excepted.
Define the value of the release object for the
night closure
. Using the release object,
the night closure can be deactivated at short-notice.
The brightness below which the "night" is recognised is set in the "façades" menu (see
Twilight
, Seite 90).
You can define that the
time and night closure
are only performed once per period/
night. Then also set the movement position.
Heat protection
Above a certain outdoor temperature, a heat protection can be travelled to. Further pa-
rameters for heat protection are set in the "façades" menu (see
Heat protection
, Seite
100).
Define the value of the release object. Using the release object, the heat protection can
be deactivated at short-notice.
Set the movement position.
If heat protection is used, then, as a precaution, protection is activated, if over a period
of 48 hours no change in the measured value has been recorded at the relevant tem-
perature sensor.
Pyranometer (global radiation)
Above a certain global radiation value, a protection position can be taken up.
Evaluation of the timed closure-release
object
1 = activated | 0 = deactivated
0 = activated | 1 = deactivated
value until first call
0 • 1
Night and timed closure only once
No • Yes
Position for night or timed closure
Movement position (in %)
0 ... 100
Slat position (in %)
(only for window shades with slats)
0 ... 100
Evaluation of the heat protection object
1 = activated | 0 = deactivated
0 = activated | 1 = deactivated
value until first call
0 • 1
Position for heat protection
Movement position (in %)
0 ... 100
Slat position (in %)
(only for window shades with slats)
0 ... 100; 90