114
Parameter setting
Weather Station Suntracer KNX sl
• Version: 14.07.2016 • Technical changes and errors excepted.
(timer function via an external device). If several devices are used in the system, the
timer settings may be done on one device that sends the period objects as output. The
other devices take over the timer-command (input), whereby a better synchronisation
is achieved.
Activate the required periods for the weekly timer. The menus for the further setting of
the computer are then loaded.
6.21.1. Weekly timer period 1-24
Set whether the period can be set (period object is the output and is sent to the bus) or
if the period is received externally via the bus (period object is the input).
Period can be set (time period object is output)
Set whether the switching times are set per object and in which cases the switching
times received are to be retained. Please note that the setting "After power restoration
and programming" should not be used for the initial start-up, as the factory settings are
always used until the first call (setting via objects is ignored).
Set the switching on and off times and the days of the week for this period. If, for ex-
ample, 15:35 is set as the switch-off time, the output switches off on the change from
15:35 to 15:36.
Use period 1
No • Yes
Use ... period
No • Yes
Use period 24
No • Yes
Period
• can be set
(period object is output)
• can be switched (time period object
is output)
Use objects for switching times
No • Yes
The threshold values and delays received by the communication object
Switching data should
• not be retained
• be retained after power restoration
• be retained after power restoration and
programming
Switch on time (hours)
0 … 23
Switch on time (minutes)
0 … 59
Switch-off time (hours)
0 … 23
Switch-off time (minutes)
0 … 59
Period switches to
Monday ... Sunday
No • Yes