73
Parameter setting
Weather Station Suntracer KNX sl
• Version: 14.07.2016 • Technical changes and errors excepted.
6.13.1. Wind threshold value 1-4
Threshold value
Set, in which cases threshold values and delay times received are to be kept per object.
The parameter is only taken into consideration if the specification/ setting by object is
activated further down. Please note that the setting "After power restoration and pro-
gramming" should not be used for the initial start-up, as the factory settings are always
used until the first call (setting via objects is ignored).
Select whether the threshold value is to be specified per parameter or via a communi-
cation object.
When the
threshold value per parameter
is specified, then the value is set.
When the
threshold value per communication object
is specified, the starting val-
ue, object value limit and type of change to the threshold value are then set.
With both of the methods for specifying the threshold values the hysteresis is set.
Maintain the
threshold values and delays received via
communication objects
• never
• after power supply restoration
• after power supply restoration and
programming
.
Threshold value setpoint using
Parameter • Communications object
Threshold value in 0.1 m/s
1 … 350; 40
Start threshold value in 0.1 m/s
valid until first call
1 … 350; 40
Object value limit (min.) in 0.1 m/s incre-
ments
1 … 350
Object value limit (max.) in 0.1 m/s incre-
ments
1 … 350
Type of threshold change
Absolute value • Increase/decrease
Step size
(upon increase/decrease change)
0.1 m/s • 0.2 m/s • 0.5 m/s • 1.0 m/s • 2.0 m/s
• 5.0 m/s
Hysteresis setting
in % • absolute
Hysteresis in % (relative to threshold value)
(for setting in %)
0 … 100; 50
Hysteresis in 0.1 m/s
(for absolute setting)
0 … 350; 20