90
Parameter setting
Weather Station Suntracer KNX sl
• Version: 14.07.2016 • Technical changes and errors excepted.
The duration of the blocking can be specified by parameter or received as an object via
the bus.
When specifying the blocking duration
by object
the minimum and maximum block-
ing duration and the increment for the change to the parameter are also defined.
Rain automation
For external shades either a rain alarm or a rain automation can be set which have op-
posite functions. The selection is made in the menu
Façades: Façade X safety
.
The rain alarm protects the shading against getting wet. The rain automation ensures
that the shading is, under certain conditions, extended during rainfall. The curtain can
thus be cleaned by natural means. Please observe the specifications from the manu-
facturer of the curtain and set the rain alarm or automation accordingly.
If a rain automation has been set for the shading, then the extension delay can be spec-
ified directly via parameter or received as an object via the bus.
Rain alarm: Shading is retracted as soon as precipitation is signalled and is blocked
during the precipitation.
Rain automation: Precipitation is only considered in pre-set periods. A rain position is
approached. The extension delay during precipitation can be set.
Twilight
Set the twilight threshold value. The threshold value can be specified directly by pa-
rameter or received as an object via the bus. The device's internally measured value is
used for brightness. The switching delay between day and twilight is 1 minute.
Preset automation blocking duration per
Parameter • object
Automation blocking duration after wind
and rain alarm (in minutes)
(for definition via an object only valid until
first call)
0 ... 360; 5
Minimum automation blocking duration
0 ... 360
Maximum automation blocking duration
0 ... 360; 30
Blocking duration increment
0 ... 50; 1
Preset extension delay for rain automation
per
Parameter • object
Extension delay on rain automation (in
minutes)
(for definition via an object only valid until
first call)
0 ... 360; 5
Preset threshold value for twilight per
Parameter • object
Night is determined at a light level below
(in Lux)
(for definition via an object only valid until
first call)
1 ... 200; 10