77
Parameter setting
Weather Station Suntracer KNX sl
• Version: 14.07.2016 • Technical changes and errors excepted.
With both of the methods for specifying the threshold values the hysteresis is set.
Switching output
Define which value the output transmits if the threshold value is exceeded or undercut.
Set the delay for the switching and in which cases the switch output transmits.
Block
If necessary, activate the switching output block and set what a 1 or 0 at the block entry
means and what happens in the event of a block.
The behaviour of the switching output on release is dependent on the value of the pa-
rameter "Switching output sends" (see "Switching output")
Hysteresis setting
in % • absolute
Hysteresis in % (relative to threshold value)
(for setting in %)
0 … 50; 20
Hysteresis in 10 Pa
(for absolute setting)
0 … 11000; 100
When the following conditions apply,
the output is
(LV = Threshold value)
• GW above = 1 | GW - Hyst. below = 0
• GW above = 0 | GW - Hyst. below = 1
• GW below = 1 | GW + Hyst. above = 0
• GW below = 0 | GW + Hyst. above = 1
Delays can be set via objects
(in seconds)
No • Yes
Delay from 0 to 1
none • 1 s … 2 h
Delay from 1 to 0
none • 1 s … 2 h
Switching output sends
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Cycle
(if sent periodically)
5 s ... 2 h
Use switching output block
No • Yes
Analysis of the blocking object
• At value 1: block | At value 0: release
• At value 0: block | At value 1: release
Blocking object value before first call
0 • 1
Action when locking
• Do not send message
• send 0
• send 1
Action upon release
(with 2 seconds release delay)
[Dependent on the "Switching output
sends" setting]
Switching output sends on change
do not send message •
Status object/s send/s