105
Parameter setting
Weather Station Suntracer KNX sl
• Version: 14.07.2016 • Technical changes and errors excepted.
Brightness threshold value
Select whether the brightness threshold value is to be specified per parameter or via a
communication object. Please observe that the communication object outputs the
threshold value in
Lux
the threshold value, however is set in
Kilolux
.
Set the brightness threshold value and the hysteresis for the event that the value is not
reached. If the value is specified via communication object, then a starting value and
the possible setting range is defined.
Travel delays
For the shading there are three travel delays:
The
extension delay
defines the waiting time for the sun automation after the bright-
ness threshold value has been exceeded.
At the end of the
short delay time
after the brightness value has not been reached an
intermediate position is approached. For example, here a position can be defined that
only differs from the shading position "extended" by the slat position on the shutter.
The shade does not immediately go up, but lets in somewhat more light. This position
is set further down in the same menu.
The
retraction delay
defines the waiting time for the retraction after the brightness
threshold value has not been reached.
Select whether the travel delay is to be specified per parameter or via objects.
Threshold value definition for
brightness per
Parameter • object
Threshold value (in kLux)
(
when specified by parameter:
valid until first call)
1 ... 150; 60
Minimum threshold value that can be set
(in kLux)
(for specification by parameter)
1 ... 150; 10
Maximum threshold value that can be set
(in kLux)
(for specification by parameter)
1 ... 150; 80
Increment for threshold value (kLux)
(for specification by parameter)
1 ... 5; 5
Hysteresis threshold value in
in percent (%) • in kLux
Hysteresis of the threshold value
(in kLux)
(in %)
1 ... 150; 20
0 ... 100; 30
Specifying the withdrawal and
extension delay
Parameter • object