Installation and Adjustment

EN

Suntracer KNX sl

 

Weather Station

Item number 70154

Elsner Elektronik GmbH

 Control and Automation Technology

Sohlengrund 16

75395 Ostelsheim 

Phone +49(0)7033/30945-0 

[email protected]

Germany 

Fax  +49(0)7033/30945-20 www.elsner-elektronik.de

Technical support: +49 (0) 70 33 / 30 945-250

Содержание Suntracer KNX sl

Страница 1: ...Installation and Adjustment EN Suntracer KNX sl Weather Station Item number 70154...

Страница 2: ...1 List of all communications objects 17 6 Parameter setting 57 6 0 1 Behaviour on power failure power restoration 57 6 0 2 Storage of threshold values 57 6 0 3 Malfunction objects 57 6 1 General sett...

Страница 3: ...6 17 4 Slat types and determination of width and spacing 82 6 17 5 Slat position for horizontal slats 83 6 17 6 Slat position for vertical slats 85 6 18 Simulation 86 6 19 Status output 87 6 20 Fa ad...

Страница 4: ...eshooting of the device must only be carried out by a competent electrician Safety advice Safety advice for working on electrical connections components etc DANGER indicates an immediately hazardous s...

Страница 5: ...4 Clarification of signs...

Страница 6: ...nd strength is measured electronically and thus noiselessly and reliably even during hail snow and sub zero temperatures Even turbulent air and rising winds in the vicinity of the device are recorded...

Страница 7: ...for wall mounting Use fixing materials that are suitable for the base 1 1 Technical specification Housing Plastic Colour White Translucent Assembly Surface mount Protection category IP 44 Dimensions...

Страница 8: ...d secure it against unintentional use if it can be assumed that risk free operation is no longer guaranteed The device is only to be used for its intended purpose Any improper modification or failure...

Страница 9: ...of clearance must be left around the device This facilitates correct wind speed measurement without eddies At the same time this prevents spray raindrops hitting the device or snow snow penetration fr...

Страница 10: ...ice must be attached to a vertical wall or a pole wall or pole 90 Fig 3 The device must be mounted in the horizontal transverse direction Horizontal Fig 4 For installation in the northern hemisphere t...

Страница 11: ...water e g rain can get into it 1 Fig 5 1 GPS receiver in lid 2 Programming LED 3 Brightness measurement 4 Precipitation sensor in lid 5 Temperature measurement 6 Wind measurement 7 Programming key on...

Страница 12: ...wall or pole installation Wall installation Use fixing materials dowels screws that are suitable for the base Fig 6 Slacken both screws on the lid top and low er part bottom with a Phillips screwdrive...

Страница 13: ...drilling plan is included ex works and this can be used as a tem plate Fig 9 a b a If the power lead is to be hidden when in stalled it must emerge from the wall in the vicinity of the rear of the hou...

Страница 14: ...4 3 Connection The connector is in the lower part of the housing Fig 11 Dimensions in mm Variations are possible for technical reasons A B2 longitudinal holes 8 mm 5 5 mm C Position of the cable outl...

Страница 15: ...asurement value and thus also all wind switching outputs cannot be out put until 35 seconds after the power is turned on Fig 14 Connect KNX data and power supply 12 40V DC 12 28V AC 1 2 to the connect...

Страница 16: ...g the address 15 15 250 or teach the device using the programming button The programming button can be reached through the opening on the underside of the housing it is recessed by approx 15 mm Use a...

Страница 17: ...o technical changes The device must regularly be checked for dirt twice a year and cleaned if necessary In case of severe dirt the sensor may not work properly anymore ATTENTION The device can be dama...

Страница 18: ...e 3 bytes 27 Time Output RWCT 10 1 DPT_TimeOfDay 3 bytes 28 Date and time query Input WC 1 017 DPT_Trigger 1 bit 30 Location Northern latitude Output R CT 14 7 DPT_Value_An gleDeg 4 bytes 31 Location...

Страница 19: ...rom 0 to 1 Input WC 7 5 DPT_TimePeriod Sec 2 bytes 61 Temp threshold value 2 Switching delay from 1 to 0 Input WC 7 5 DPT_TimePeriod Sec 2 bytes 62 Temp threshold value 2 Switching output Output R CT...

Страница 20: ...sor threshold value 2 Absolute value Input Output RWCT 9 4 DPT_Value_Lux 2 bytes 109 Brightness sensor threshold value 2 1 0 Input WC 1 1 DPT_Switch 1 bit 110 Brightness sensor threshold value 2 Delay...

Страница 21: ...solute value Input Output RWCT 9 4 DPT_Value_Lux 2 bytes 137 Brightness sensor 2 threshold value 2 1 0 Input WC 1 1 DPT_Switch 1 bit 138 Brightness sensor 2 threshold value 2 Delay from 0 to 1 Input W...

Страница 22: ...2 Absolute value Input Output RWCT 9 4 DPT_Value_Lux 2 bytes 165 Brightness sensor 3 threshold value 2 1 0 Input WC 1 1 DPT_Switch 1 bit 166 Brightness sensor 3 threshold value 2 Delay from 0 to 1 Inp...

Страница 23: ...ld value 2 Absolute value Input Output RWCT 9 4 DPT_Value_Lux 2 bytes 193 Total brightness threshold value 2 1 0 Input WC 1 1 DPT_Switch 1 bit 194 Total brightness threshold value 2 Delay from 0 to 1...

Страница 24: ...2 Absolute value Input Output RWCT 9 4 DPT_Value_Lux 2 bytes 221 Twilight brightness threshold value 2 1 0 Input WC 1 1 DPT_Switch 1 bit 222 Twilight brightness threshold 2 delay from 0 to 1 Input WC...

Страница 25: ...sor Measurement m s Output R CT 9 5 DPT_Value_Wsp 2 bytes 273 Wind sensor Measurement Beaufort Output R CT 20 014 DPT_Beau fort_Wind_Force_S cale 1 byte 274 Wind sensor Max query measure ment Input WC...

Страница 26: ...shold value 4 Delay from 1 to 0 Input WC 7 5 DPT_TimePeriod Sec 2 bytes 303 Wind threshold value 4 Switching output Output R CT 1 1 DPT_Switch 1 bit 304 Wind threshold value 4 Switching output block I...

Страница 27: ...1 bit 423 Air pressure threshold value 3 Absolute value Input Output RWCT 14 58 DPT_Value_ Pressure 4 bytes 424 Air pressure threshold value 3 1 0 Input WC 1 1 DPT_Switch 1 bit 425 Air pressure thres...

Страница 28: ...utomation Delay in min utes 1 0 Input WC 1 1 DPT_Switch 1 bit 552 Fa ade Brightness in Lux Input WCT 9 4 DPT_Value_Lux 2 bytes 553 Fa ade Twilight threshold value in kLux Input Output RWCT 9 4 DPT_Val...

Страница 29: ...it 580 Fa ade External temperature in C sim ulation Input RWC 9 1 DPT_Value_Temp 2 bytes 581 Fa ade Internal temperature in C sim ulation Input RWC 9 1 DPT_Value_Temp 2 bytes 582 Fa ade Brightness in...

Страница 30: ...DPT_Switch 1 bit 608 Fa ade 1 external temperature Block ing release block Input RWC 1 1 DPT_Switch 1 bit 609 Fa ade 1 external temperature Block in C Input Output RWCT 9 1 DPT_Value_Temp 2 bytes 610...

Страница 31: ...1 1 DPT_Switch 1 bit 634 Fa ade 1 sun automation Elevation up to in Input RWCT 14 7 DPT_Value_An gleDeg 4 bytes 635 Fa ade 1 sun automation Elevation up to 1 0 Input WC 1 1 DPT_Switch 1 bit 636 Fa ade...

Страница 32: ...ade 2 wind extension block thresh old value in m s Input RWCT 9 5 DPT_Value_Wsp 2 bytes 661 Fa ade 2 wind extension block thresh old value 1 0 Input WC 1 1 DPT_Switch 1 bit 662 Fa ade 2 wind extension...

Страница 33: ...9 1 DPT_Value_Temp 2 bytes 687 Fa ade 2 internal temperature block release block Input RWC 1 1 DPT_Switch 1 bit 688 Fa ade 2 indoor temp Block in C Input Output RWCT 9 1 DPT_Value_Temp 2 bytes 689 Fa...

Страница 34: ...1 DPT_Switch 1 bit 712 Fa ade 2 movement position Output R CT 5 1 DPT_Scaling 1 byte 713 Fa ade 2 slat position Output R CT 5 1 DPT_Scaling 1 byte 714 Fa ade 2 channel status output 1 On 0 Off Input...

Страница 35: ...On 0 Off Output R CT 1 1 DPT_Switch 1 bit 740 Fa ade 3 timed closure release block Input RWC 1 1 DPT_Switch 1 bit 741 Fa ade 3 timed closure status 1 On 0 Off Output R CT 1 1 DPT_Switch 1 bit 742 Fa a...

Страница 36: ...nput WCT 9 4 DPT_Value_Lux 2 bytes 766 Fa ade 3 sun automation Brightness threshold value in Lux Input RWCT 9 4 DPT_Value_Lux 2 bytes 767 Fa ade 3 sun automation Brightness threshold value 1 0 Input W...

Страница 37: ...nput RWCT 9 5 DPT_Value_Wsp 2 bytes 793 Fa ade 4 wind alarm threshold value 1 0 Input WC 1 1 DPT_Switch 1 bit 794 Fa ade 4 wind alarm status 1 On 0 Off Output R CT 1 1 DPT_Switch 1 bit 795 Fa ade 4 fr...

Страница 38: ...block Input RWC 1 1 DPT_Switch 1 bit 820 Fa ade 4 sun automation Azimuth from in Input RWCT 14 7 DPT_Value_An gleDeg 4 bytes 821 Fa ade 4 sun automation Azimuth from 1 0 Input WC 1 1 DPT_Switch 1 bit...

Страница 39: ...ytes 845 Fa ade 4 channel status bit state Output R CT 1 1 DPT_Switch 1 bit 846 Fa ade 4 channel delay Output R CT 7 005 DPT_TimePeri odSec 2 bytes 847 Fa ade 4 channel status bit selection 1 0 Input...

Страница 40: ...heating protection release block Input RWC 1 1 DPT_Switch 1 bit 873 Fa ade 5 heating protection status 1 On 0 Off Output R CT 1 1 DPT_Switch 1 bit 874 Fa ade 5 pyranometer release block Input RWC 1 1...

Страница 41: ...htness Long status 1 On Output R CT 1 1 DPT_Switch 1 bit 898 Fa ade 5 extension delay in min Input Output RWCT 7 006 DPT_TimePeri odMin 2 bytes 899 Fa ade 5 extension delay in min 1 0 Input WC 1 1 DPT...

Страница 42: ...Off Output R CT 1 1 DPT_Switch 1 bit 926 Fa ade 6 timed opening release block Input RWC 1 1 DPT_Switch 1 bit 927 Fa ade 6 timed opening status 1 On 0 Off Output R CT 1 1 DPT_Switch 1 bit 928 Fa ade 6...

Страница 43: ...n Elevation from in Input RWCT 14 7 DPT_Value_An gleDeg 4 bytes 953 Fa ade 6 sun automation Elevation from 1 0 Input WC 1 1 DPT_Switch 1 bit 954 Fa ade 6 sun automation Elevation up to in Input RWCT 1...

Страница 44: ...979 Fa ade 7 wind extension block 1 On 0 Off Input RWC 1 1 DPT_Switch 1 bit 980 Fa ade 7 wind extension block thresh old value in m s Input RWCT 9 5 DPT_Value_Wsp 2 bytes 981 Fa ade 7 wind extension b...

Страница 45: ...put R CT 1 1 DPT_Switch 1 bit 1006 Fa ade 7 internal temperature in C Input WCT 9 1 DPT_Value_Temp 2 bytes 1007 Fa ade 7 internal temperature block release block Input RWC 1 1 DPT_Switch 1 bit 1008 Fa...

Страница 46: ...TimePeri odMin 2 bytes 1031 Fa ade 7 retraction delay in min 1 0 Input WC 1 1 DPT_Switch 1 bit 1032 Fa ade 7 movement position Output R CT 5 1 DPT_Scaling 1 byte 1033 Fa ade 7 slat position Output R C...

Страница 47: ...C 1 1 DPT_Switch 1 bit 1059 Fa ade 8 external temperature Block status 1 On 0 Off Output R CT 1 1 DPT_Switch 1 bit 1060 Fa ade 8 timed closure release block Input RWC 1 1 DPT_Switch 1 bit 1061 Fa ade...

Страница 48: ...1 DPT_Switch 1 bit 1085 Fa ade 8 sun automation Brightness measurement in Lux Input WCT 9 4 DPT_Value_Lux 2 bytes 1086 Fa ade 8 sun automation Brightness threshold value in Lux Input RWCT 9 4 DPT_Valu...

Страница 49: ...Input RWCT 4 bytes 1151 Computer 2 Input I3 Input RWCT 4 bytes 1152 Computer 2 Output O1 Output R CT 4 bytes 1153 Computer 2 Output O2 Output R CT 4 bytes 1154 Computer 2 Condition text Output R CT 1...

Страница 50: ...T 4 bytes 1190 Computer 7 Input I2 Input RWCT 4 bytes 1191 Computer 7 Input I3 Input RWCT 4 bytes 1192 Computer 7 Output O1 Output R CT 4 bytes 1193 Computer 7 Output O2 Output R CT 4 bytes 1194 Compu...

Страница 51: ...Switch 1 bit 1230 Weekly timer period 5 8 bit output Output R CT 5 10 DPT_Value_1_U count 1 byte 1231 Weekly timer period 6 Switch on time Input RWCT 10 1 DPT_TimeOfDay 3 bytes 1232 Weekly timer perio...

Страница 52: ...Switching out put Output R CT 1 1 DPT_Switch 1 bit 1258 Weekly timer period 12 8 bit output Output R CT 5 10 DPT_Value_1_U count 1 byte 1259 Weekly timer period 13 Switch on time Input RWCT 10 1 DPT_...

Страница 53: ...Switching out put Output R CT 1 1 DPT_Switch 1 bit 1282 Weekly timer period 18 8 bit output Output R CT 5 10 DPT_Value_1_U count 1 byte 1283 Weekly timer period 19 Switch on time Input RWCT 10 1 DPT_...

Страница 54: ..._U count 1 byte 1331 Calendar timer period 1 Start date Input RWCT 11 1 DPT_Date 3 bytes 1332 Calendar timer period 1 End date Input RWCT 11 1 DPT_Date 3 bytes 1333 Calendar timer period 1 sequence 1...

Страница 55: ...Output R CT 5 10 DPT_Value_1_U count 1 byte 1357 Calendar timer period 3 sequence 2 Switch on time Input RWCT 10 1 DPT_TimeOfDay 3 bytes 1358 Calendar timer period 3 sequence 2 Switch off time Input R...

Страница 56: ...bit 1415 AND logic 2 1 bit switching output Output R CT 1 2 DPT_Bool 1 bit 1416 AND logic 2 8 bit output A Output R CT 1 byte 1417 AND logic 2 8 bit output B Output R CT 1 byte 1418 AND logic 2 Block...

Страница 57: ...output B Output R CT 1 byte 1454 OR logic 3 Block Input WC 1 1 DPT_Switch 1 bit 1455 OR logic 4 1 bit switching output Output R CT 1 2 DPT_Bool 1 bit 1456 OR logic 4 8 bit output A Output R CT 1 byte...

Страница 58: ...e first communication of a new threshold value After this a threshold value once set per parameter or via a communication object is retained until a new threshold value is sent via a communication obj...

Страница 59: ...he event of a GPS malfunction Please note that after return of auxiliary voltage it can take up to 10 minutes before the GPS signal is received 6 2 Location The location data is required in order to b...

Страница 60: ...is selected Belgium Denmark Germany France Great Britain Italy Liechtenstein Luxembourg Netherlands Austria Switzerland USA Town if input by town is selected 6 towns in Belgium 1 town in Denmark 48 to...

Страница 61: ...Prefix positive negative Hours 0 13 1 Minutes 0 59 0 Summertime rule Europe USA user defined none All the following times are to be entered as winter time standard time Start of Summer Time on Monday...

Страница 62: ...p as the factory settings are always used until the first call setting via objects is ignored Select whether the special rain output is to be used with fixed switching delay This switching output has...

Страница 63: ...s required maximum four The menus for the further setting of the threshold values are then displayed Switching output sends on change on change to rain on change to no rain on change and periodically...

Страница 64: ...et When the threshold value per communication object is specified the starting val ue object value limit and type of change to the threshold value are then set With both of the methods for specifying...

Страница 65: ...s can be set via objects in seconds No Yes Delay from 0 to 1 none 1 s 2 h Delay from 1 to 0 none 1 s 2 h Switching output sends on change on change to 1 on change to 0 on change and periodically on ch...

Страница 66: ...ttern for the measured brightness Switching output sends on change to 1 and periodically If switching output 1 send 1 Switching output sends on change to 0 and periodically If switching output 0 send...

Страница 67: ...as the factory settings are always used until the first call setting via objects is ignored Select whether the threshold value is to be specified per parameter or via a communi cation object When the...

Страница 68: ...ease change 1000 2000 5000 10000 20000 Hysteresis setting in absolute Hysteresis in of the threshold value for setting in 0 100 50 Hysteresis in Lux for absolute setting 0 150000 30000 When the follow...

Страница 69: ...not be used for the initial start up as the factory settings are always used until the first call setting via objects is ignored Action upon release with 2 seconds release delay Dependent on the Switc...

Страница 70: ...ter Communications object Threshold value in kLux 1 1000 10 Start threshold value in Lux valid until first call 1 1000 10 Object value limit min in Lux 1 1000 Object value limit max in Lux 1 1000 Type...

Страница 71: ...ignored Use switching output block No Yes Analysis of the blocking object At value 1 block At value 0 release At value 0 block At value 1 release Blocking object value before first call 0 1 Action wh...

Страница 72: ...ognised below Lux 1 1000 10 Hysteresis in Lux 0 500 5 Delays can be set via objects in seconds No Yes Switching delay on night none 1 s 2 h Switching delay on day none 1 s 2 h Switching output sends o...

Страница 73: ...he menus for the further setting of the threshold values are then displayed Send pattern never periodically on change on change and periodically on change of if sent on change 2 5 10 25 50 Send cycle...

Страница 74: ...shold value per communication object is specified the starting val ue object value limit and type of change to the threshold value are then set With both of the methods for specifying the threshold va...

Страница 75: ...s can be set via objects in seconds No Yes Delay from 0 to 1 none 1 s 2 h Delay from 1 to 0 none 1 s 2 h Switching output sends on change on change to 1 on change to 0 on change and periodically on ch...

Страница 76: ...the pressure compensated for height and temperature The bar ometric air pressure is the pressure measured directly by the sensor without compen sation Switching output sends on change to 1 and periodi...

Страница 77: ...Seite 38 Select whether the threshold value is to be specified per parameter or via a communi cation object When the threshold value per parameter is specified then the value is set When the threshold...

Страница 78: ...0 50 20 Hysteresis in 10 Pa for absolute setting 0 11000 100 When the following conditions apply the output is LV Threshold value GW above 1 GW Hyst below 0 GW above 0 GW Hyst below 1 GW below 1 GW Hy...

Страница 79: ...60529 Point 1 External temperature 20 Target value 20 C Point 2 External temperature 32 Target value 26 C Set the send pattern for the summer compensation Switching output sends on change to 1 do not...

Страница 80: ...ent on change 0 1 C 0 2 C 0 5 C 1 C 2 C 5 C Send cycle if sent periodically 5 s 2 h 1 min Use block No Yes Analysis of the blocking object At value 1 block At value 0 release At value 0 block At value...

Страница 81: ...nclination of the fa ade Alignment and slant of the fa ade are needed for the shadow edge tracking and the slat auto guide Example If the building is skewed by 30 then the direction for fa ade 1 30 fa...

Страница 82: ...top downwards e g shutters textile shades or blinds with horizontal slats This function cannot be used with sunshades which are pulled in front of a window from one or both sides Slat tracking During...

Страница 83: ...imum permitted penetration depth e The slats can be set horizontally without the sun shining directly into the room e Sunshade when the sun is in a central posi tion Fig 24 The sunshade is automatical...

Страница 84: ...e does In order for slat tracking to set the slats correctly their width and spacing from one an other must be known 6 17 5 Slat position for horizontal slats The slat angle at 0 move command and at 1...

Страница 85: ...ng is 10 The angle is always measured to the vertical perpendicular Slat position at 0 After moving to the 0 slat position the slats form another angle with the vertical This must be entered in the pa...

Страница 86: ...perly Slat position at 100 After moving to the 100 slat position the slats form an angle with the direction of movement This angle must be entered in the parameter Slat angle in after slat move comman...

Страница 87: ...bjects number 576 to 591 different weather conditions and times of day can be tested With the object 590 fa ade simulation reset 1 Reset you can delete all the simulation values that were set Activati...

Страница 88: ...the simula tion object for date and time sent to the bus In order that this functions a location must be set in the product parameters or the location received via GPS As long as the location is unkn...

Страница 89: ...seconds No Identification Range Function Info 568 Fa ade X channel Status output Activation Set to active in order to use the status output 569 Fa ade X channel Name Fa ade Output of the fa ade name w...

Страница 90: ...d use wind and rain ob ject monitoring If data is not regularly being received from the sensors a defect is as sumed and the corresponding alarm is triggered Independently of live monitoring the measu...

Страница 91: ...n object via the bus Rain alarm Shading is retracted as soon as precipitation is signalled and is blocked during the precipitation Rain automation Precipitation is only considered in pre set periods A...

Страница 92: ...hold value by object the minimum and maximum values that can be set for temperature and the increment for the change are also defined Frost alarm This frost alarm is only used within the fa ade contro...

Страница 93: ...n an external temperature of in 0 1 C is not reached for definition via an object only valid until first call 200 300 20 during or until in hours after precipitation for definition via an object only...

Страница 94: ...Time open Free text Outdoor temperature block Outd temp Sp free text Time night closure Time night clo free text Heat protection Heat protection Free text Pyranometer Pyranometer Free text Rain autom...

Страница 95: ...un on fac Free text Sun bright short retraction delay Status Bright short Free text Sun bright long retraction delay Status Bright long Free text Name Fa ade 1 Free text Use simulation objects No Yes...

Страница 96: ...commands If the wind alarm is used then as a precaution the alarm is activated if over a period of 48 hours no change in the measured value has been recorded at the relevant wind sensor Set with what...

Страница 97: ...s a precaution the alarm is activated if over a period of 48 hours no change in the measured value has been recorded at the relevant out door temperature sensor Rain In the event of precipitation eith...

Страница 98: ...can be deactivated at short notice Define the follow up time The follow up time is the delay time after the end of the pre cipitation warning Within the automation functions the rain automation has a...

Страница 99: ...Us ing the release object time opening can be deactivated at short notice Outdoor temperature block Below a certain outdoor temperature the shade is withdrawn Set whether an outdoor temperature block...

Страница 100: ...d For the timed closure set in which periods of the week and the calendar timer the timed closure movement position is to be travelled to The periods are defined in the menu week timer or month timer...

Страница 101: ...release object the heat protection can be deactivated at short notice Set the movement position If heat protection is used then as a precaution protection is activated if over a period of 48 hours no...

Страница 102: ...ecorded at the relevant pyranometer Rain automation If rain protection has configured as rain automation then its priority is between the pyranometer controller and the interior temperature block Rain...

Страница 103: ...then the position of the sun and the brightness are checked and is corresponding to the solar protection automation shaded Set whether solar protection automation is to be used Define the value of the...

Страница 104: ...a wall or overhanging roof can also be taken into account in the setting for sun direction azimuth and sun height elevation Fig 34 1a Sun elevation Azimuth In the morning the building is fully shaded...

Страница 105: ...select which brightness value sensor is to be relevant for the shading of the fa ade As a brightness value the highest value actually measured by the three internal sensors can be used or a value tha...

Страница 106: ...termediate position is approached For example here a position can be defined that only differs from the shading position extended by the slat position on the shutter The shade does not immediately go...

Страница 107: ...to Extension delay in minutes when specified by parameter valid until first call 1 240 Minimum extension delay that can be set in minutes for specification by parameter 1 240 Maximum extension delay t...

Страница 108: ...p slat guiding the fixed movement position and the four slat angles are defined only for shades with slats For the slat guiding the fixed movement position and the characteristics of the fa ade and th...

Страница 109: ...move command is to be transmitted the frequency of the position correction can be adjusted Hereby the technical possibilities of the drive used must be taken into consideration See also chapter Shadow...

Страница 110: ...Standard movement position Solar protection automation is terminated and the standard position is approached the sun is not coming from the set shading direction or the brightness is then below the va...

Страница 111: ...lways used until the first call setting via objects is ignored Select the function set the input mode and starting values for input 1 and input 2 Evaluation of the fa ade Status release object 1 activ...

Страница 112: ...h symbol 4 byte floating point Starting value E1 E2 E3 Input range depending on the type of input Output type 1 bit 1 byte 0 255 1 byte 0 100 1 byte 0 360 2 byte counter without math symbol 2 byte cou...

Страница 113: ...met on change to condition not met Send cycle if sent periodically 5 s 2 h 10 s Text if the condition is met Free text max 14 chars Text if the condition is not met Free text max 14 chars Send delay...

Страница 114: ...n the device 24 periods can be defined These periods are for ex ample used for the internal automatic function timed opening and timed closure The respective period objects can be configured as inputs...

Страница 115: ...nd in which cases the switching times received are to be retained Please note that the setting After power restoration and programming should not be used for the initial start up as the factory settin...

Страница 116: ...for the further setting of the computer are then loaded 6 22 1 Calendar clock Period 1 4 Set whether the switching date and the switching time are set per object and in which cases the switching date...

Страница 117: ...p to and including Month January December Day 1 29 1 30 1 31 according to month Switch on time hours 0 23 Switch on time minutes 0 59 Switch off time hours 0 23 Switch off time minutes 0 59 Switching...

Страница 118: ...t or two 8 bit objects Determine what the out put should send if logic 1 and 0 8 bit output value if Period active 0 255 8 bit output value if Period not active 0 255 Use logic inputs Yes No Object va...

Страница 119: ...1 0 255 100 360 127 1 Output value object B if logic 1 0 255 100 360 127 1 Output value object A if logic 0 0 255 100 360 127 0 Output value object B if logic 0 0 255 100 360 127 0 Output value object...

Страница 120: ...put 2 inverted Logic input 3 Logic input 3 inverted Logic input 4 Logic input 4 inverted Logic input 5 Logic input 5 inverted Logic input 6 Logic input 6 inverted Logic input 7 Logic input 7 inverted...

Страница 121: ...N GPS malfunction OFF Wind Sensor malfunction ON Wind sensor malfunction OFF Switching output rain Switching output rain inverted Switching output rain 2 Switching output rain 2 inverted Switching out...

Страница 122: ...re inverted Wind switching output 1 Wind switching output 1 inverted Wind switching output 2 Wind switching output 2 inverted Wind switching output 3 Wind switching output 3 inverted Wind switching ou...

Страница 123: ...tive Weekly timer period 23 active Weekly timer period 23 inactive Weekly timer period 24 active Weekly timer period 24 inactive Calendar timer period 1 sequence 1 active Calendar timer period 1 seque...

Страница 124: ...put 1 inverted AND logic output 2 AND logic output 2 inverted AND logic output 3 AND logic output 3 inverted AND logic output 4 AND logic output 4 inverted AND logic output 5 AND logic output 5 invert...

Страница 125: ...GmbH Control and AutomationTechnology Sohlengrund 16 75395 Ostelsheim Phone 49 0 7033 30945 0 info elsner elektronik de Germany Fax 49 0 7033 30945 20 www elsner elektronik de Technical support 49 0...