UPServer2.0
ON-LINE DOUBLE CONVERSION
EN 6100-4-5, Livello 4 Criterio A
EMC
certifications
CE per IEC/EN 62040-2,
Classe B
EMC (Emission)
IEC 62040-2:ed2:2005 / EN 62040-2:2006
Safety
IEC 62040-1-1, IEC 60950-1
Marking
CE, CB
Operating
temperature
0°C to 40°C (32°F to 104°F) in Online mode, with linear derating for altitude
NOTE Thermal protection switches load to Bypass in case of overheating.
Humidity
0
–90% noncondensing
Operataing
altitude
Up to 3,000 meters (9,843 ft) above sea level
Audible Noise
<55 dBA a 1 m typical
Leakage current
<1.5 mA
8. TROUBLESHOOTING
The following messages are the information that users would find on UPS when it meets some
problems. Users can judge if the fault is caused by external factors and know how to deal with it
by making full use of the information.
Fault indicator on, indicates that the UPS has detected some faults. Buzzer beeps, indicates that
UPS need to be paid attention to, if beeps for a long time, it means that there is something wrong
with the machine. If you need help, contact our service department, the following messages
should be provided for analysis:
◆UPS MODEL NO. and SERIAL NO.
◆Date of fault happened
◆ Detailed description of the problem (include indicator
statements on cover)
the following table describes typical alarm conditions.
Table 22.
ault
Cause
Solution
The “INPUT”
letters on LCD
display section
flashes
Anti-connection of
mains live and neutral
or mains is out of
range
Re-connect the input power cable
and make a correct connection
Battery capacity
indicator flashes
Battery low voltage or
battery disconnected
Check UPS battery, connect
battery well, if battery damaged,
replace it
Mains normal, but
UPS has no input
UPS input breaker
open circuit
Press the breaker for reset
Short back up time
Battery not fully
charged
Keep UPS connecting with mains
power for more than 8 hours,
recharge battery
UPS overload
Check the usage of loads, remove
some redundant devices