UPServer2.0
ON-LINE DOUBLE CONVERSION
CAUTION
A small amount of arcing may occur when connecting the internal batteries. This is
normal and will not harm personnel. Connect the cables quickly and firmly
.
Figure8 Connecting the UPS Internal Batteries
3.
If you are installing EBPS, see the following section, “Connecting the EBP(s),” before
continuing with the UPS installation.
4.
Replace the UPS front cover.
To replace the cover, verify the EBP cable is routed through the knockout on the bottom of
the cover if EBPS are installed.
Put the front cover hooks of side with display to the cover port, put another side to the
other two ports, then press it until the cover and the chassis are combined tightly.
Figura 9
5.
If you are installing power management software, connect your computer to one of the
communication ports or optional connectivity card. For the communication ports, use an
appropriate cable.
6.
If your rack has conductors for grounding or bonding of ungrounded metal parts,