UPServer2.0
ON-LINE DOUBLE CONVERSION
● First, turn on the generator, after it runs stably connect output power of the
generator to UPS input terminal, then turn on the UPS. After the UPS is turned
on, please connect load one by one.
● It is recommended that the generator capacity is as twice as the UPS rated
capacity.
● You had better not use the ECO mode when the quality of the input AC mains is
not good.
5 COMMUNICATION RS232, USB, OPTIONALS AND EPO
This section describes the:
● Communication ports (RS-232 and USB)
● Connectivity cards
● Emergency Power-off (EPO)
● Load Segments
● UPSilon2000 Power Management Software
Installing Communication Options and Control Terminals
To install the communication options and control terminals:
1.
Install the appropriate connectivity card and/or necessary cable(s) and
connect the cables to the appropriate location.
2.
Route and tie the cable(s) out of the way.
3.
Continue to “Operation” on page 26/28 to start up the UPS.
Communication Options
The UPS has serial communication capabilities through the USB and RS-232
communication ports or through a connectivity card in the available
communication bay. The UPS supports two serial communication devices
according to the following table:
NOTE
:
The communication speed of the RS232 port is fixed at 2400 bps.
RS-232 and USB Communication Ports
To establish communication between the UPS and a computer, connect your computer to one of
the UPS communication ports using an appropriate communication cable (not supplied). See