UPServer2.0
ON-LINE DOUBLE CONVERSION
Model
Connection type
Cable
UPserver 2.0
IEC320 C13-10A
IEC320 C14-10A
Table 17. Output
Nominal Value
200/208/220/230/240V
(Configurable or auto-sensing)
2000 VA
1350 W
Frequency
50 or 60 Hz, auto-sensing
Overload
(Normal operation)
108%±5%
–150%±5%: Load transfers to Fault mode after 30 seconds.
150%±5%
–200%±5%: Load transfers to Fault mode after 300 ms.
>200%±5%: Load transfers to Fault mode after 20 ms.
Overload
(Bypass mode)
100%±5%
–130%±5%: Load transfers to Fault mode after 20 minutes..
130%±5%
–150%±5%: Load transfers to Fault mode after 2 minutes.
150%±5%
–200%±5%: Load transfers to Fault mode after 15 seconds.
>200%±5%: Load transfers to Fault mode after 140 ms.
Overload
(Battery mode)
108%±5%
–150%±5%: Load transfers to Fault mode after 30 seconds..
150%±5%
–200%±5%: Load transfers to Fault mode after 300 ms.
>200%±5%: Load transfers to Fault mode after 300 ms.
Voltage Waveform
Sine wave
Harmonic Distortion
<3% THD on linear load; <5% THD on non-linear load
Transfer time
Online mode: 0 ms (no break)
ECO mode: 10ms maximum (due to loss of utility)
Load Crest Factor
3 a 1
Table 18. Output electrical connections
Model
Output connections
Cable
UPserver 2.0
(IEC C13-10A)*2 + 1 Shuko
IEC320 C14-10A
Table 19. Environmental and Safety
Surge
Suppression
EN 61000-2-2
EN 61000-4-2, Livello 4
EN 61000-4-3, Livello 3
EN 61000-4-4, Livello 4