ON-LINE DOUBLE CONVERSION
Replacing Tower EBPs
CAUTION
The EBP is heavy. Lifting the cabinet requires a minimum of two people.
1. Unplug the EBP cable from the UPS. If additional EBPs are installed, unplug the EBP cable from
the battery connector on each EBP.
2. Replace the EBP(s). See “Recycling the Used Battery or UPS” on page 62 for proper disposal.
3. For each replaced EBP, remove the cable retention clip covering the battery connector(s), as
shown in Figure 17 on page 25. Retain the clips.
4. Plug the EBP cable(s) into the battery connector(s) as shown in Figure 17 on page 25. Up to four
EBPs may be connected to the UPS.
5. Retain the removed clips.
6. Verify that the EBP connections are tight and that adequate bend radius and strain relief exist
for each cable.
Replacing RT UPS and EBPS
1. If the battery fault, the following steps are provided for modular unit to replace the new
battery pack
2. Remove the front cover of the battery box.
3. Remove the connection cables between battery box and UPS. Release the screw of the
baffle of the battery pack as the Fig26 shows, then remove the baffle from the left or right.