UPServer2.0
ON-LINE DOUBLE CONVERSION
than half a second(less than 2
seconds) at this time, the letters
“bPS” will stop flashing. The
“ON”(or OFF) below the bPS
will flash. Press and hold the
scroll key
for more than half a
second (less than 2 seconds) to
determine whether the BPS
function is enabled or disabled.
③
Confirm the BPS selecting
interface. After selecting ON
or OFF, press and hold the
function setting key
for
more than half a second
(less than 2 seconds). Now,
the BPS setting function is
completed and the “ON”
or “OFF” below the
“bPS” will light without
flashing.
④ If you choose “OFF”, then
go to step 7, otherwise go
ahead to step 5.
⑤ Set the BPS tolerance range.
Short press the scroll
key
or
for more than
half a second (shorter than 2
seconds)to
select
the
voltage range in percentage.
+5%,+10%,+15%,+25%(def
ault is +25%) , then short
press function setting key
for more than half a
second (shorter than 2
seconds)to
confirm
the
selection, then to set the
minus range
⑥ To set the minus range in the
same way.
⑦ After the minus range is
confirmed. Long press function
setting key
for more than 2
seconds to exit setting menu.
Output
voltage
setting(3)
① Enter the setting interface.
Press and hold the function
setting key
for more than
2 seconds, then come to
setting interface, Press and
hold the scroll key
for
more than half a second(less
than 2 seconds), select the
function setting, choose
output
voltage
setting
interface, at the moment, the
letters “OPU” will flash.
② Enter the output voltage
selecting interface. Press and
hold the function setting
key
for more than half a
second(less than 2 seconds),