UPServer2.0
ON-LINE DOUBLE CONVERSION
UPSilon2000 Power Management Software
Each UPS ships with UPSilon2000 Power Management Software. To begin
installing UPSilon2000 software, see the instructions accompanying the Software
Suite CD.
NOTE
Install UPSilon2000 power management software with the serial number
attched on the cover of the CD .When running the monitor software , choose
appropriate communication port. If using RS232, choose COM1/2 and Megatec
protocol. If using USB, choose megatec USB.
UPSilon2000 software provides up-to-date graphics of UPS power and system
data and power flow. It also gives you a complete record of critical power events,
and it notifies you of important UPS or power information. If there is a power
outage and the UPS battery power becomes low, UPSilon2000 software can
automatically shut down your computer system to protect your data before the
UPS shutdown occurs.
6
UPS Maintenance
UPS and Battery Care
For the best preventive maintenance, keep the area around the UPS clean and
dust‐free. If the atmosphere is very dusty, clean the outside of the system with a
vacuum cleaner. For full battery life, keep the UPS at an ambient temperature of
25°C (77°F).
NOTE
The batteries in the UPS are rated for a 3–5 year service life. The length of
service life varies, depending on the frequency of usage and ambient
temperature. Batteries used beyond expected service life will often have severely
reduced runtimes. Replace batteries at least every 5 years to keep units running
at peak efficiency.
Storing the UPS and Batteries
If you store the UPS for a long period, recharge the battery every 6 months by
connecting the UPS to utility power. The internal batteries charge to 80%
capacity in less than 5 hours. However, we recommends that the batteries charge
for 48 hours after long-term storage.
Replacing Batteries
NOTE
DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
。
The EBP can be replaced when UPS is ON, but be aware that if the utility fails at
that time , the load of the UPS may NOT be protected.