For this function only use external sensors (from bus) can be used, such as the ekinex EK-SM2-TP movement sensor
or the ekinex EK-DX2-TP (X = B, C, D, E) presence sensor. The following condition has to be true:
External sensors (from bus) Presence sensor 1 (from bus) or Presence sensor 2 (from bus) = enabled
•
11.8.2.1 Parameter and communication object tables
Parameter name
Conditions
Values
Presence sensors function
disabled
/ enabled
Parameter that enables the presence sensor function.
Presence sensors use
Presence sensor function = enabled
comfort extension
comfort limitation comfort
extension and comfort
limitation
Thermostat modes
Presence sensor function = enabled,
Presence sensors use = comfort
extension and comfort limitation or =
comfort limitation
comfort-standby
comfort-economy
Absence time to switch HVAC mode
Presence sensor function = enabled
00:01:00 hh:mm:ss
[range
00:00:00 … 18:12:15]
Time interval before the automatic switching of the operating mode set in the
Thermostat modes parameter.
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj. No.
Presence sensor 1 (from bus)
Presence sensor function=
enabled
1 Bit
C-W---
[1.018]
occupancy
15
Presence sensor 2 (from bus)
Presence sensor function =
enabled
1 Bit
C-W---
[1.018]
occupancy
16
9.10.3 Card holder
The
Card holder
secondary folder appears only if the corresponding sensor is enabled i.e. if the following condition is
true: External sensors (from bus) Card holder contact = enabled
The
Card holder
folder includes the following parameters:
•
Card holder function
•
On card insertion switch HVAC mode to
•
Activation delay on card insertion
•
On card removal switch HVAC mode to
•
Activation delay on card removal