Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj.
No.
Comfort setpoint (heating)
2 Byte
CRWTU-
[9.001] temperature (°C)
29
Standby setpoint (heating)
2 Byte
CRWTU-
[9.001] temperature (°C)
31
Economy setpoint (heating)
2 Byte
CRWTU-
[9.001] temperature (°C)
33
Building protection setpoint
(heating)
2 Byte
CRWTU-
[9.001] temperature (°C)
35
Heating out command
Control type = 2 points
hysteresis or PWM,
Command communication
object = separated
1 Bit
CR-T--
[1.001] switch
38
Heating out command
Control type = continuous,
Command communication
object = separated
1 Byte
CR-T--
[5.001] percentage (0..100%)
38
Heating and cooling out
command
Tipo Control type = 2 points
hysteresis or PWM,
Command communication
object = unique
1 Bit
CR-T--
[1.001] switch
38
Heating and cooling out
command
Control type = continuous,
Command communication
object = unique
1 Byte
CR-T--
[5.001] percentage (0..100%)
38
Auxiliary heating out command
Auxiliary heating = enabled,
Command communication
object = separated
1 Bit
CR-T--
[1.001] switch
40
Auxiliary heating and cooling
output command
Auxiliary heating = enabled,
Command communication
object = unique
1 Bit
CR-T--
[1.001] switch
40
Auxiliary heating disable
Auxiliary heating = enabled,
1 Bit
C-W--- [1.003] enable 42
Disabled from bus = yes
Temperature setpoint change
lock
1 Bit
C-W---
[1.003] enable
37
About floor temperature limitation function
The floor heating system (warm water version) provides plastic pipes embedded in the concrete layer or placed directly
under the final coating of the floor (light or "dry" system) filled by heated water. The water releases heat to the final
coating that heats the room by radiation. The standard EN 1264 Floor heating (Part 3: Systems and components -
Dimensioning) prescribes a maximum allowed temperature (T
Smax
) for the surface of the floor that is physiologically
correct defined as:
•
T
Smax
≤ 29°C for zones of normal occupancy;