9.6
Cooling
The
Cooling
folder includes the following parameters:
•
Comfort temp. setpoint [°C]
•
Standby temperature setpoint [°C]
•
Economy temp. setpoint [°C]
•
Building protection temp. setpoint [°C]
•
Cooling type
•
Control type
•
Hysteresis
•
Cyclic sending interval
•
Min. change of value to send [%]
•
PWM cycle time
•
Proportional band [0,1 K]
•
Integral time [min]
•
Anticondensation with probe
•
Anticondensation protection type 2
•
Auxiliary cooling
•
Disabled from bus
•
Offset from setpoint
•
Hysteresis ON/OFF [K]
9.6..1 Parameter and communication object tables
Conditions:
General
Thermostat function = cooling or both heating and cooling.
Parameter name
Conditions
Values
Comfort temp. setpoint [°C]
23
[range 10 … 50]
Standby temp. setpoint [°C]
26
[range 10 … 50]
For a correct operation of the device the standby temperature setpoint has to be >
comfort temperature setpoint.
Economy temp. setpoint [°C]
28
[range 10 … 50]
For a correct operation of the device the standby temperature setpoint has to be >
economy temperature setpoint.
Building protection temp. setpoint [°C]
36
[range 30 … 50]
Cooling type
fan-coils
floor radiant panels ceiling
radiant panels
If in Settings the parameter Thermostat function = both heating and cooling and
Command communication object = unique, the parameter Cooling type is bound to the
choice done for Heating.
Control type
Command communication object =
separated
2 point hysteresis
PWM (pulse width modulation)
continuous
If in Settings the parameter Thermostat function = both heating and cooling and
Command communication object = unique, the parameter Control type is bound to the
choice done for Heating.