Applicatio Manual
Universal Interface 4 DIN/NTC EK- CG2-TP
Revisione 1.0.0 - Aggiornato: 04/09/2017
© SBS S.p.A.
– Tutti i diritti riservati
MAEKCG2TP_EN
Pag. 72
Signal from bus
Disable dehumid. control from bus = yes
not inverted
/ inverted
Object name
Conditions
Dim.
Flags
DPT
Comm. Obj. No.
Relative humidity setpoint for
dehumidification
2 Byte
CRWTU-
[9.007] humidity (%)
58
Dehumidification command
1 Bit
CR-T--
[1.001] switch
60
Dehumidification water battery
command
Temperature control
Settings
Thermostat
function = both
heating and
cooling,
Temperature
control cooling
cooling type = floor
radiant panels or
ceiling radiant
panels,
Relative humidity
dehumidification
dehumidification
function = cooling
1 Bit
CR-T--
[1.001] switch
61
Dehumidification integration
control
Temperature control
Settings
Thermostat
1 Bit
CR-T--
[1.001] switch
62
Object name
Conditions
Dim.
Flags
DPT
Comm. Obj. No.
function = both
heating and
cooling,
Temperature control
cooling
cooling type = floor
radiant panels or
ceiling radiant
panels,
Relative humidity
dehumidification
dehumidification
function = cooling
This object switches ON if (simultaneously) the relative humidity is greater than the relative
humidity setpoint and the room temperature is greater than the setpoint of the parameter
Temperature difference for integration.
Dehumidification control disable
1 Bit
C-W---
[1.002] boolean
63