9.5 Heating
The
Heating
folder includes the following parameters:
•
Comfort temp. setpoint [°C]
•
Standby temperature setpoint [°C]
•
Economy temp. setpoint [°C]
•
Building protection temp. setpoint [°C]
•
Heating type
•
Control type
•
Hysteresis
•
Cyclic sending interval
•
Min. change of value to send [%]
•
PWM cycle time
•
Proportional band [0,1 K]
•
Integral time [min]
•
Floor temperature limitation
•
Temperature limit [°C]
•
Hysteresis [K]
•
Auxiliary heating
•
Communication object
•
Disabled from bus
•
Offset from setpoint
•
Hysteresis
•
Cyclic sending interval
•
Ventilation for auxiliary heating
9.5.1 Parameter and communication object tables
Conditions:
Settings
Thermostat function = heating or both heating and cooling.
Parameter name
Conditions
Values
Comfort temp. setpoint [°C]
21
[range 10 … 50]
Standby temp. setpoint [°C]
18
[range 10 … 50]
For a correct operation of the device the standby temperature setpoint has to be <
comfort temperature setpoint.
Economy temp. setpoint [°C]
16
[range 10 … 50]
For a correct operation of the device the economy temperature setpoint has to be <
standby temperature setpoint.
Building protection temp. setpoint [°C]
7
[range 2 … 10]
Heating type
radiators
electric
fan-coils
floor radiant panels ceiling
radiant panels