Disable ventilation from bus
no
/ yes
Parameter name
Conditions
Values
Signal from bus
Disable ventilation from bus =
yes
not inverted
inverted
Fan start delay
0 s
[other values in the range 10 s …
12 min]
It appears also if the hot-start function is active (through measuring of
the conveying fluid temperature at the battery for the thermal
exchange). The function is active in both seasonal modes (heating
and cooling).
Fan stop delay
0 s
[other values in the range 10 s …
12 min]
The function allows prolonging the operation of the ventilator,
dissipating in the room the residual heat or cool present in battery for
the thermal exchange. The function is active in both seasonal modes
(heating and cooling).
Cyclic sending interval
no sending
[other values in the range 30 s …
120 min]
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj.
No.
Fan continuous speed
Control type =
continuous
regulation
1 Byte
CR-T--
[5.001] percentage (0..100%)
44
Fan speed 1
Control type = 1, 2
o 3 speeds
1 Bit
CR-T--
[1.001] switch
45
Fan speed 2
Control type = 2 or 3
speeds
1 Bit
CR-T--
[1.001] switch
46
Fan speed 3
Control type = 3
speeds
1 Bit
CR-T--
[1.001] switch
47
Fan control disable
Disable ventilation
from bus = yes
1 Bit
C-W---
[1.002] boolean
48
Fan manual speed
1 Byte
CRWTU-
[5.010] counter pulses (0…255)
51
Fan speed status
1 Byte
CR-T--
[5.010] counter pulses (0…255)
52