9.9.1 Dehumidification
The secondary folder
Humidification
includes the following parameters:
•
Operating modes where dehumidification is active
•
Relative humidity setpoint for dehumidification control [%]
•
Dehumidification control hysteresis [%]
•
Dehumidification secondary to temperature control
•
Function of integration of sensible heat
•
Disable from bus
9.9.1.1
Parameter and communication object tables
Parameter name
Conditions
Values
Dehumidification function
disabled
cooling
heating
both cooling and heating
Parameter that selects the dehumidification function.
Humidity setpoint [%]
Dehumidification function ≠ disabled
55
[range 30 … 60]
Hysteresis
Dehumidification function ≠ disabled
0,8 %
[other values in the range 0,5 … 4%]
Subordinated to temperature control
Temperature control Settings
Thermostat function = both heating and
cooling,
Temperature control cooling cooling
type = floor radiant panels or ceiling
radiant panels,
Relative humidity dehumidification
dehumidification function = cooling
no /
yes
Dehumidification start delay
Subordinated to temperature control =
no
00:05:00 hh:mm:ss
[range
00:00:00 … 18:12:15]
Value 00:00:00 means that the start delay is disabled.
Integration
no
/ yes
Temperature difference for integration
Integration = yes
1,5°C
[other values in the range 0,5 … 3°C]
Hysteresis for integration
Integration = yes
0,5 K
[other values in the range 0,2 K … 3 K]
Cyclic sending interval
no sending
[other values in the range 30 s … 120
min]
Value 00:00:00 means that the cyclic sending is disabled.
Disable dehumid. control from bus
no
/ yes