Applicatio Manual
Universal Interface 4 DIN/NTC EK- CG2-TP
Revisione 1.0.0 - Aggiornato: 04/09/2017
© SBS S.p.A.
– Tutti i diritti riservati
MAEKCG2TP_EN
Pag. 43
Object name
Conditions
Dim.
Flags
DPT
Comm.
Obj. No.
Temperature value
Temperature sensor = enabled
2 Bytes
CR-T--
[9.001]
temperature (°C)
Temperature threshold1 - Switch
Temperature sensor = enabled,
Threshold 1 = below or above
1 Bit
CR-T--
[1.001] switch
Temperature threshold 2- Switch
Temperature sensor = enabled,
Threshold 2 = below or above
1 Bit
CR-T--
[1.001] switch
9.2.2 Acquisition filter
The acquisition filter calculates an average with a series of measured values before sending on the bus. The parameter
can have the following values:
low = average value every 4 measurements;
medium = average value every 16 measurements;
high = average value every 64 measurements.
9.2.3 Correction of the measured temperature
The sampling of the temperature value occurs every 10 seconds, while the display is updated every minute. During the
configuration with ETS the opportunity is given to correct the measured temperature value within the offset range of - 5
°C ... + 5 °C (step: 0.1 K).