Chapter 6 Parameter Description
72
To facilitate the operation, the frequent operation can be set on the multi-functional key of the operation
panel.
0: No function.
1: Jog function: For the jog frequency and jog acceleration/deceleration time, refer to P3.11~P3.13.
2: Emergency shutdown 1: Applicable to the situation that may cause human danger. The motor will be
stopped with the shortest deceleration time.
3: Emergency shutdown 2: Applicable to the situation that may cause electric equipment damage. The
motor will be stopped freely.
4: Realize the circular switching of the operating command reference modes (operation panel reference
→terminal reference→host computer reference). The MON status LED on the
operation panel will
indicate the corresponding status. It is effective only when the PRG key is pressed within 5 seconds,
otherwise, the switching will be invalid, and the MON LED will restore to the former indication state.
5: Realize the circular switching of the display modes of fast function codes and all the function codes.
6: Realize the circular switching of the display modes of function codes different from leave-factory
values and all the function codes.
7: Realize the circular switching of the display modes of last changed 10 function codes and all the
function codes.
8: Realize the circular switching of different function code display modes (basic menu mode
→
fast menu
mode
→
menu mode of non-leave-factory value function code
→
Menu mode of last changed 0 function
codes, refer to description of P0.02 for the menu modes.
Up to 4 parameters can be set and display at running status, and viewed circularly by pressing >>key.
Display of operation panel
Unit place:
0: Reference frequency (Hz) ;
1: Bus voltage (V) ;
2: AI1 (V) ;
3: AI2 (V) ;
4: AI3 (V) ;
5: DI (%) ;
6: External counts
7: Motor rotation speed (rpm);
8: Close loop reference (%);
9: Close loop feedback (%);
A: Reference torque (%);
B: Operating frequency (Hz);
C: Output current (A);
D: Output torque (%);
E: Output power (kW);
F: Output voltage (V)
Tens place
Same as above
Hundreds place
Same as above
Thousands place
Same as above
P2.01
Multi-functional key definition
0~8(1)
Display parameter selection at running
P2.02
0~FFFF(1CB0)