V&T Technologies Co., Ltd.
http://www.ecodrivecn.com
Chapter 7 Fault Diagnosis
125
Failure No.
Failure code
Failure description
Potential causes
Solutions
30
E.Ptc
Motor over
temperature(PTC)
The motor temperature
signal reaches the alarm
setting value
Strengthen ventilation and
radiation
Thermistor resistance
failure
Check the thermistor
The sensor protection
threshold of the motor is
set improperly
Adjust the sensor protection
threshold of the motor
31
E.SE1
Communication
abnormal 1
(Operation panel
485)
The communication of
operation panel 485 is
disconnected
Check the connection of the
equipment communications
The communication of
operation panel 485 is
faulty
Check whether the data
receiving and transmission
complies with the protocol,
whether the check sum is
correct and whether the
receiving and transmission
interval complies with the
requirements
The inverter is set to
master mode
Set the inverter to slave mode
32
E.SE2
Communication
abnormal 2
(Terminal 485)
The communication of
terminal 485 is
disconnected
Check the connection of the
equipment communications
The baud rate is set
improperly
Set compatible baud rate
The communication of
terminal 485 is faulty
Check whether the data
receiving and transmission
complies with the protocol,
whether the check sum is
correct and whether the
receiving and transmission
interval complies with the
requirements
The communication of
terminal 485 is time-out
Check whether the
communication timeout is set
properly and confirm the
communication cycle of the
application program
The failure alarm
parameter is set
improperly
Adjust the failure alarm
parameter
The inverter is set to
master mode
Set the inverter to slave mode
33
E.VEr
Version compatibility
abnormal
The software version of the
operation panel is
incompatible
Seek for technical support
34
E.CPy
Copy failure
The data error appears
when copying the inverter
parameters to the
operation panel
Check the connections of the
operation panel
The data error appears
when copying the
parameters from the
operation panel to the
inverter
Check the connections of the
operation panel