Chapter 6 Parameter Description
115
Quadrant I: F orward
running driving
Quadrant II: Reverse
running braking
Quadrant III: R everse
running driving
Quadrant IV: Forward
running braking
Pd.09
Pd.08
Pd.08
Pd.09
Output
torque
Motor
speed
Fig. 6-36 Torque limit
Note: When setting P9.00 to 1, i.e. operating with variable torque load, the setting range of Pd.08 and
Pd.09 change to 0.0~150.0%. The leave-factory value is 135.0%
Pre-magnetizing is to create magnetize flux before the motor starts, aiming at fast response upon starting
up of the motor. When operation instructions are available, bring the inverter into the pre-magnetizing
status in the time set by this function code. After establishing the magnetize flux, try to accelerate
normally. If the function code is set to 0, no pre-magnetizing process is applied.
Note: The motor may rotate during pre-magnetizing, and then adopt mechanical braking additionally.
Pd.10
Reserved
0~65535(4)
Pd.11
Reserved
0.000~65.535(0.010)
Pd.12
Reserved
0~120.00s(0.10s)
Pd.13
Reserved
0~120.00s(0.10s)
Pd.14
Pre-magnetizing time
0.000~8.000 s(0.300s)