Menu structure UA 300 D
Controller type UR 141
88
Version 2.03 27. Juni 2008
ALARM 1A
POS: XXXXX
Entry
Default
High Temp Setp
XX °C
High temperature setpoint at which
High Temperature
alarm
is generated
−30..30
−12 °C
Low Temp Setp.
XX K
Low temperature setpoint (difference below temperature
control setpoint) at which
Low Temperature
alarm is gene-
rated
−−, 0..6
2 K
S
Screen 2−4−4 Zone 2A Altern.
ALARM 2A
POS: XXXXX
Entry
Default
High Temp Setp
XX °C
High temperature setpoint at which
High Temperature
alarm
is generated
−30..30
10 °C
Low Temp Setp.
XX K
Low temperature setpoint (difference below temperature
control setpoint) at which
Low Temperature
alarm is gene-
rated
−−, 0..6
2 K
7.3.4
Menu 3 Clock
CLOCK
POS: XXXXX
1 Current Time
Continue to Screen 3−1
2 Defrost timer
Continue to Screen 3−2
3 Toggle Setpoints
Continue to Screen 3−3
S
Screen 3−1 Current Time
Time default is set by the time master (CI 3000, AL 300) when CAN bus is connected. Any entry
made will then be overwritten by the default value.
CLOCK
POS: XXXXX
Entry
Default
Date: XX dd.mm.yy
Display and enter current weekday, date
dd.mm.yy
Time: hh.mm
Display and enter current time
hh.mm
Daylight Saving
X
Display and enter automatic daylight saving change (Y/N)
↑
,
↓
, (Y/N)
J
Содержание UA 300 D
Страница 2: ......
Страница 6: ...Table of contents iv Version 2 03 27 Juni 2008 Notice ...
Страница 8: ...System Design of UA 300 D 2 Version 2 03 27 Juni 2008 Notice ...
Страница 40: ...Installation and Startup of UA 300 D 34 Version 2 03 27 Juni 2008 Notice ...
Страница 54: ...Operation of UA 300 D 48 Version 2 03 27 Juni 2008 Notice ...
Страница 100: ...Menu structure UA 300 D Controller type UR 141 94 Version 2 03 27 Juni 2008 Notice ...
Страница 108: ...Specifications of UA 300 D 102 Version 2 03 27 Juni 2008 Notice ...